HomeProductsValvesInnovations for AutomationInformation Request E-Mail
Valve IP 65 Profibus / Interbus MWP

With its sturdy construction and IP65 protection, the bus module can be mounted directly on the outside of the machine or system without requiring additional protection. Sensors and/or actuators can be connected via highly reliable M12 plugs. Available for PROFIBUS-DP and INTERBUS-S IP 65 Profibus / Interbus
TECHNICAL DATA PROFIBUS-DP INTERBUS-S
Versions 8 outputs 8 outputs
16 inputs 16 inputs
8 imputs + 4 outputs 8 inputs + 4 outputs
Supply voltage   24 Vdc (18V......30V), approx. 100 mA
Degree of protection IP65
Temperature 0÷55°C (32÷131°F)
Field Bus data Transmission protocol Profibus-DP DIN E 19245 Interbus-S DIN E 19258
Transmission method Synchronous or Freeze-Mode  
Transfer speed 12MBit/s 500KBit/s
Addresses Rotary switches BCD, 3...99  
Input technical data Type pnp proximity sensors or IEE 1131-2 compatible mechanical limit switches
Voltage 24VDC (from 18V to 30V) , max. 100mA simultaneously
Indicator light Each input has a LED
Output technical data Voltage 24VDC (from 18V to 30V) max. voltage 2A for each actuator
Max. exchange current 2A, system protected by short-circuit fuse
Max. connectable load 10W
Max. signal exchange frequency 100 Hz Ohm, 1 Hz induction
Indicator light Each output has a LED
Autotest Field bus RUN-LED BA-,RD-,RC-LEDs
Insuff. voltage signal LED + alarm signal to master
INPUT short-circuit sensor LED + alarm signal to master
OUTPUT short-circuit sensor LED + alarm to master
NB: The slaves come complete with cable glands    
COMPONENTS
  1. In-out connectors
    When the Slave is 8 OUT, each connector corresponds to an OUT. When the Slave is 16 IN, each connector corresponds to 2 IN.
  2. In-out connectors
  3. Autotest LED
  4. IN power connector
  5. OUT power connector
  6. Connector for IN bus
  7. Connector for OUT bus
Componets