HomeProductsValvesInnovations for AutomationInformation Request E-Mail
Valve IP 20 Profibus / Interbus MWP

The IP20 bus module is the package type and can easily be mounted inside control panels or cubicles. Available in various configurations designed for PROFIBUS-DP and INTERBUS-S IP 20 Profibus / Interbus
TECHNICAL DATA PROFIBUS-DP INTERBUS-S
Versions           16 inputs / 32 inputs 16 inputs / 32 inputs
16 outputs 16 outputs
16 inputs + 16 outputs 16 inputs + 16 outputs
Supply voltage   24 Vdc (18V......30V), approx. 100 mA
Degree of protection   IP20
Temperature   0÷55°C (32°÷131°F)
Field Bus data       Transmission protocol Profibus-DP DIN E 19245 Interbus-S DIN E 19258
Transmission method Synchronous or Freeze-Mode
Transfer speed 12MBit/s 500KBit/s
Addresses Rotary switches BCD, 3...99  
Input technical data     Type 1,2,3,4 wires to IEC 1131-2
Voltage 24VDC (from 18V to 30V) total 1.6A
Indicator light Each input has a LED
Output technical data         Voltage 24VDC (from 18V to 30V) total current 8A to 32A
Max. exchange current each output 0.5A (on request 2A)
Max. connectable load 2W
Max. signal exchange frequency 100 Hz Ohm, 1 Hz induction
Indicator light Each output has a LED
Autotest       Field bus RUN-LED BA-,RD-,RC-LEDs
Voltage signal LED + alarm signal
INPUT short-circuit sensor LED + alarm signal to master
OUTPUT short-circuit sensor LED + alarm to masteR
NB: The slave comes complete with a terminal block set    
COMPONENTS
  1. Earth
  2. +24 for inductance
  3. Bus voltage Ø
  4. Bus voltage +24V
  5. Autotest LED
  6. Output
  7. Input
  8. Ø V for output
  9. Bus in/out
  10. Slave addresses
Componets